2通道隔离屏障、24 V直流电源(电源轨)、干触点或NAMUR输入、隔离无源晶体管输出、TTL电平、线路故障检测(LFD)、可逆操作模式

信号类型:数字输入
连接:电源导轨或端子14+,15
额定电压:20 ...30 V DC
Ripple:≤10?%
Rated current:≤50 mA
Connection side:field side
Connection:terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values:acc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Open circuit voltage/short-circuit current:approx.8 V DC /约8 mA
切换点/切换滞后:1.2 ...2.1毫安/约0.2 mA
线路故障检测:破损I ≤0.1 mA,短路I > 6 mA
连接侧:控制侧
连接:输出I:端子7+, 8-;输出II:端子10+, 11-
切换电压:最大。30 V
开关电流:最大2 mA,短路保护
信号级别:1-信号:开关电压 - 0.85 V max.在2 mA开关电流
0信号:关闭(关闭状态电流≤10 µA)
输出I, II:信号,TTL兼容
集合错误信息:电源轨
开关频率:≤5 kHz
输入/输出:增强绝缘 acc.到IEC 62103,额定绝缘电压300 Vrmsrms
输入/电源:电源:inforced绝缘符合IEC 62103,额定绝缘电压300 Vrms
输出/电源:电源:根据IEC 62103,额定绝缘电压 50 V输出/输出:基本绝缘电压 50 V<60 °C (-4...140 °F)
Degree of protection:IP20
Connection:screw terminals,Mass:approx. 150 g
Dimensions:20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mounting:on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate:PTB 00 ATEX 2035
Supply:
Output:
EU-type examination certificate:DMT 01 ATEX E 133
Certificate:TüV 99 ATEX 1499 X
Galvanic isolation:
Directive conformity:
FM?approval:
IECEx approval:
Supplementary information:Observe the certificates, declarations of conformity declarations of conformity, instruction

上一篇:P+F KFD2-SR2-Ex2.2S

下一篇:P+F KFD2-SR2-Ex2.W

相关内容

P+F KFD2-SOT2...
2通道隔离屏障、24 V直流电源(电源轨)、干触点或NAMUR输入...
2023-11-08 17:19:13

热门资讯

P+F KCD2-ST-Ex1... 1通道隔离屏障,24 V直流电源(电源轨),干触点或NAMUR输入,2个有源晶体管输出,可用作信号分...
P+F KCD2-SON-Ex... 2通道隔离屏障,24 V直流电源(电源轨),干触点或NAMUR输入,2个无源晶体管输出(电阻符合EN...
P+F KCD2-SON-Ex... 1通道隔离屏障,24 V直流电源(电源轨),干触点或NAMUR输入,2个无源晶体管输出(电阻符合EN...
P+F KFD2-SOT3-E... 2通道隔离屏障,24 V直流电源(电源轨),干触点或NAMUR输入,隔离无源晶体管输出,TTL电平,...
P+F KFD2-DU-Ex1... 1通道隔离屏障,24 V直流电源(电源轨),干触点或NAMUR输入,继电器触点和晶体管输出,可调节输...
P+F KFA6-DU-Ex1... 1通道隔离屏障,230V交流电源,干触点或NAMUR输入,继电器触点和晶体管输出,可调输出定时器功能...
P+F KFA5-SOT2-E... 2通道隔离屏障,115 V交流电源,干触点或NAMUR输入,无源晶体管输出,非极化,线路故障检测(L...
P+F KCD2-SOT-Ex... 1通道隔离屏障,24 V直流电源(电源轨),干触点或NAMUR输入,2个无源晶体管输出,可用作信号分...
P+F WE 77/Ex-2 ... 2通道,控制电路EEx ia IIC,115 V交流电源电压,可逆操作模式,导线断裂(LB)监测,每...
P+F KFD2-ST3-Ex... 2通道隔离屏障、24 V直流电源(电源轨)、干触点或NAMUR输入、有源晶体管输出、线路故障检测(L...